REBOILER HEATER TUBE FIRE(2003) | 2006.06.30 | ||
---|---|---|---|
작성자 : 관리자 | 첨부파일(1) | ||
【제 목】: REBOILER HEATER TUBE FIRE(2003) 【발행처】: KOSHA-CCPS 【발행일】: 2004년 10월
【요 약】
REBOILER HEATER TUBE FIRE
This report explains the fire that occurred on October, 2003 in a HOU(Heavy Oil Upgrading) Plant, Ulsan, Korea. The fire was arisen due to corrosion of fire heater tube, which was the convection heater tube of pre-fractionator reboiler and released VGO(Vacuum Gas Oil) that ignited. No employee was injured, but potentially polluted material was released into the air. The key safety issues covered in this report were how to inspect the convection heater tube and to select proper tube material of construction at the stage of design. Recommendations concerning this issue were delivered to said Plant.
|